We can identify the poor quality of steel doors when we buy them. As a low-cost and convenient fireproof partition, steel fireproof glass door has played a very important role in preventing the spread of fire and smoke and ensuring the dispersion of personnel. In the field of construction engineering and application, the following quality problems often occur:
I. The fire resistance integrity of steel fireproof glass door is poor. Some enterprises take the road of low-cost and defective products in daily production. The products are shoddy or the quality control in the device link is not strict, resulting in serious overspending of various gap widths such as door leaf, mouth seam, frame leaf seam, door leaf and ground seam, which can not meet the technical requirements of the standard rules due to fire leakage during inspection. In the actual project, some steel fire doors are not equipped with door closers, sequencers and sealing strips, which seriously affects the fire and smoke separation function of steel fire-proof glass doors and should be found in time.
II. Some steel fireproof glass doors use inappropriate sealing materials to hinder the opening and closing of the door leaf. The design gap between the door frame and the door leaf is too small, and the quality of the door closer is too poor, resulting in too large opening force and reaction force, which will affect the opening and closing of the fireproof door. During inspection, the problem can be found only by on-site operation and opening and closing the fire door several times.
III. poor thermal insulation of door leaf. The filling material of steel fireproof glass door is generally aluminum silicate fiber or rock wool. The fire resistance of aluminum silicate fiber is significantly better than rock wool, but the price is higher. In the field of application, attention should be paid to the phenomenon that many manufacturers use cheap rock wool to replace the aluminum silicate fiber actually used in type inspection. If the glass area is too large, it is generally difficult for the door leaf as a whole to meet the requirements of fire integrity and heat insulation. When checking, you can actually measure the glass area and thickness, whether it is fireproof glass, etc.
The good or bad quality of steel fireproof glass door directly affects the improper treatment of the gap between thermal insulation materials, resulting in poor thermal insulation of the door leaf.
Fire door http://www.huhaiming.com/
05-04
What are the problems of composite fireproof glass in fire fighting
Some supervisors mistakenly think that the door made of fireproof glass is the fireproof door, the partition made of fireproof glass is the fireproof glass partition, and the window made of fireproof
04-12
Fireproof glass door: how to ensure that the fireproof door can play a role in critical times
How to ensure that the fire door can give full play to its ideal effect in critical time?1. Select appropriate typesAccording to the relevant specific introduction of fire doors, we can know that at t
02-17
Where is the fireproof glass generally installed
(1) the fireproof glass is generally installed on something. It may not be checked from time to time before installation. If the warpage, unsightness and glass hazards of the window edge and window ar
10-30
How to distinguish the quality of single fireproof glass?
1. Equipment conditions:No matter how to make a single piece of fireproof glass, it can't be done without some equipment, so if the manufacturer doesn't have the equipment, it can't mak